Product overview:

FZN21-12D/T630-20 type indoor high-voltage vacuum load open three-phase AC 50Hz indoor high voltage switch equipment, suitable for rated voltage 12kV distribution system. Switch with closing bearing breaking load and the current load ability; can also be disconnected, closing the no-load long line, no-load transformer and capacitor.

FZN21-12DR/T125-31.5 type indoor high-voltage vacuum load switch fuse combined electrical apparatus, the load switch and fuse combination and become, in addition to having the functions also has protection function.


Use environment:

No more than 1000 meters of sea level;

The ambient air temperature is not higher than +40, and no less than -10;

Air relative humidity is not more than 90% of the indoor places (when the temperature is +25 DEG C);

In the environment of non conducting dust;

An object that has no damage to the metal and the corrosive gas;

No violent vibration and impact;

There is no danger of burning and explosion.


Technical parameters:

1, the main technical parameters of load switch:


Number Item Unit Data

1    rated voltage kV 12

2    rated frequency Hz 50

3  rated current A 630

4    rated active load current A 630

5    rated closed loop breaking current A 630

6    5% rated active load current A 31.5

7   rated cable charging breaking current A 10

8   rated no-load transformer capacity kVA 1250

9    1min power frequency withstand voltage: (vacuum fracture, interphase, relative / isolated fracture) kV 42/48

10   lightning impulse withstand voltage: (vacuum fracture, interphase, relative / isolated fracture) kV 75/85

11 rated short-time withstand current (thermal stability) kA/S 20/4

12    rated peak withstand current (thermal stability) kA 5

13    rated short-circuit current kA 50

14   rated current number of times 次 10000

15    mechanical life times 次 10000

16    the contact of the vacuum arc extinguishing chamber allows the wear thickness mm 2

17    manual force distance Nm ≤200


2、 the main technical parameters of the combination of electrical appliances:

Number Item Unit Data

1    rated voltage kV 12

2   rated frequency Hz 50

3    maximum rated current A 125

4   rated breaking current A 3150

5    Switching time of fuse ms 40±5

6    rated short-circuit breaking current(virtual value)

kA 31.5

7  rated short circuit off current(peak value) kA 50

8   1min power frequency withstand voltage: (vacuum fracture, interphase, relative / isolated fracture) kV 42/48

9  lightning impulse withstand voltage: (vacuum fracture, interphase, relative / isolated fracture) kV 75/85

10   the output of the fuse 2-5 J J 2-5

Appearance and installation dimensions