Indoor high-voltage vacuum load switch
- Introduction
- Parameters
- Pictures Show
Product overview:
FZN21-12D/T630-20 type indoor high-voltage vacuum load open three-phase AC 50Hz indoor high voltage switch equipment, suitable for rated voltage 12kV distribution system. Switch with closing bearing breaking load and the current load ability; can also be disconnected, closing the no-load long line, no-load transformer and capacitor.
FZN21-12DR/T125-31.5 type indoor high-voltage vacuum load switch fuse combined electrical apparatus, the load switch and fuse combination and become, in addition to having the functions also has protection function.
Use environment:
No more than 1000 meters of sea level;
The ambient air temperature is not higher than +40, and no less than -10;
Air relative humidity is not more than 90% of the indoor places (when the temperature is +25 DEG C);
In the environment of non conducting dust;
An object that has no damage to the metal and the corrosive gas;
No violent vibration and impact;
There is no danger of burning and explosion.
Technical parameters:
1, the main technical parameters of load switch:
Number Item Unit Data
1 rated voltage kV 12
2 rated frequency Hz 50
3 rated current A 630
4 rated active load current A 630
5 rated closed loop breaking current A 630
6 5% rated active load current A 31.5
7 rated cable charging breaking current A 10
8 rated no-load transformer capacity kVA 1250
9 1min power frequency withstand voltage: (vacuum fracture, interphase, relative / isolated fracture) kV 42/48
10 lightning impulse withstand voltage: (vacuum fracture, interphase, relative / isolated fracture) kV 75/85
11 rated short-time withstand current (thermal stability) kA/S 20/4
12 rated peak withstand current (thermal stability) kA 5
13 rated short-circuit current kA 50
14 rated current number of times 次 10000
15 mechanical life times 次 10000
16 the contact of the vacuum arc extinguishing chamber allows the wear thickness mm 2
17 manual force distance Nm ≤200
2、 the main technical parameters of the combination of electrical appliances:
Number Item Unit Data
1 rated voltage kV 12
2 rated frequency Hz 50
3 maximum rated current A 125
4 rated breaking current A 3150
5 Switching time of fuse ms 40±5
6 rated short-circuit breaking current(virtual value)
kA 31.5
7 rated short circuit off current(peak value) kA 50
8 1min power frequency withstand voltage: (vacuum fracture, interphase, relative / isolated fracture) kV 42/48
9 lightning impulse withstand voltage: (vacuum fracture, interphase, relative / isolated fracture) kV 75/85
10 the output of the fuse 2-5 J J 2-5
Appearance and installation dimensions